- Corrugated Spiral Double Layer cable protective pipe suitable for Medium mechanical loads.
- Does not transmit flame, It is self –extinguished and at very low halogen concentration.
- It is used for protection of electrical cables into wall construction, plaster boards, roof boards, for surface installation, into concrete, constructural works, underground networks, external places, industrial areas and generally to places of medium mechanical loads.
RECOMMENDED FOR USE IN THE PLACE OF MEDIUM TYPE PVC PIPES.
|
Nominal Diameter
|
Internal Diameter D1(mm)
|
External Diameter D2(mm)
|
Wall Thickness
S(mm)
|
Weight (gr/m)
|
Packaging(m/roll)
|
|
11
|
11,1
|
16,5
|
0,40
|
50
|
50
|
|
13,5
|
14,9
|
20,6
|
0,40
|
65
|
50
|
|
16
|
16,8
|
21,8
|
0,45
|
80
|
50
|
|
23
|
23,3
|
28,9
|
0,50
|
115
|
25
|
|
• COMPRESSION RESISTANCE :
|
(20°C) > 320 N/5cm
|
CLASSIFICATION 2
|
|
• IMPACT RESISTANCE :
|
(-25°C) > 2 Kg/300mm
|
CLASSIFICATION 4
|
|
• WORKING TEMPERATURES
|
MIN : -25°C
|
CLASSIFICATION 4
|
|
|
MAX: +60 °C
|
CLASSIFICATION 1
|
- COLOR : EXTERNALLY LIGHT GREY, INTERNALLY DARK GREY/ BLACK WITH FULL PROTECTION AGAINST
SOLAR RADIATION
- MATERIAL : EXTERNALLY LDPE / INTERNALLY HD - PE.
- STANDARDS : ΕΝ 61386 - 1/2004, ΕΝ 61386 - 2 1/2004.
|
Due to the properties of the material of construction attains high chemical resistance to acids and alkalis offering protection against the various additives of concrete and of wall plasters.
|